Input devices, Circuit breakers/fuses, Filters, emc – Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual
Page 69: Input modes, Input power conditioning

Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013
69
Detail Drive Configuration and Operation
Chapter 1
summed torque enters the torque selection block (refer to Torque Reference on
page
for more information).
Parameter 55 [Speed Comp] contains the rate of acceleration or deceleration
calculated in the inertia compensation block. This parameter is used in following
applications. Link parameter 23 [Speed Trim 3] to [Speed Comp] and set
parameter 24 [SpeedTrim3 Scale] to 0.002 to reduce position error in following
applications.
Input Devices
For information on contactors, see Motor Start/Stop Precautions on page
Circuit Breakers/Fuses
See the PowerFlex 700S high Performance AC Drive Phase I Control, User
Manual, publication
Filters, EMC
Refer to CE Conformity on page
.
Input Modes
Refer to Start/Stop Modes on page
.
Input Power Conditioning
See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives, publication
, for detailed information.
Jog
A jog reference is usually used to run the motor at some preset, low speed. Two
separate jog speeds can be used as a speed reference - parameter 17 [ Jog Speed 1]
or parameter 18 [ Jog Speed 2]. A jog could be initiated by a Digital Input, by the
Logic Command word from a DPI Adapter such as a HIM, or by the Logic
Command word from DriveLogix. In turn, a valid jog command initiated from
one of those adapters will turn on either bit 18 in parameter 152 [Applied
LogicCmd] to select jog speed 1 or bit 23 in [Applied LogicCmd] to select jog
56
9
57
58
43
Inertia Comp
Δ
n
Δ
t
Inertia SpeedRef
InertiaAccelGain
InertiaDecelGain
Total Inertia
Logic Command
(Inertia Comp)
59
Link
S Curve Spd Ref
Inertia Torq Add
to Torque
Control [4B1]
60
DeltaSpeedScale
151
10
55
Speed Comp