Detail Drive Configuration and Operation
Chapter 1
COMM-D would have a total of 40 bytes of I/O mapped in the DeviceNet
scanner. The I/O Image table for a ControlLogix system is shown.
1
The speed reference comes into the 20-COMM-D as a double integer. The PowerFlex 700S firmware automatically converts that
speed reference into floating point, so that parameter 20 [Speed Ref DPI] is a floating-point value.
1
Bits 0-15 only of parameter 155 [Logic Status] appear in the Input Image table of the ControlLogix controller.
2
The speed feedback sent from the PowerFlex 700S to the 20-COMM-D is not affected by parameter 73 [Spd Fdbk Scale].
Furthermore, the PowerFlex 700S automatically coverts parameter 72 [Scaled Spd Fdbk], which is a floating-point parameter, to a
double integer before the value is transferred to the 20-COMM-D.
ControlLogix
Adapter
PowerFlex 700S
Output Image
O.Data[0] DINT
O.Data[1] DINT
O.Data[2] DINT
O.Data[3] DINT
O.Data[4] DINT
O.Data[5] DINT
O.Data[6] DINT
O.Data[7] DINT
O.Data[8] DINT
O.Data[9] DINT
0 Logic
Command
1 Pad
Word
2 Reference
3 Reference
4 Datalink
A1
5 Datalink
A1
6 Datalink
A2
7 Datalink
A2
8 Datalink
B1
9 Datalink
B1
1 Datalink
B2
1 Datalink
B2
1 Datalink
C1
1 Datalink
C1
1 Datalink
C2
1 Datalink
C2
1 Datalink
D1
1 Datalink
D1
1 Datalink
C2
1 Datalink
C2
P158 Drive
Logic
P20 SpeedRef
DPI
P707 Data In A1 Int
P708 Data In A1
P709 Data In A2 Int
P710 Data In A2
P711 Data In B1 Int
P712 Data In B1
713
Data In B2 Int
P714 Data In B2
P715 Data In C1 Int
P716 Data In C1
P717 Data In C2 Int
P718 Data In C2
P719 Data In D1 Int
P720 Data In D1
P721 Data In D2 Int
P722 Data In D2
DPI
DeviceNet
1
ControlLogix
Adapter
PowerFlex 700S
Input Image
I.Data[0] DINT
I.Data[1] DINT
I.Data[2] DINT
I.Data[3] DINT
I.Data[4] DINT
I.Data[5] DINT
I.Data[6] DINT
I.Data[7] DINT
I.Data[8] DINT
I.Data[9] DINT
0 Logic
Status
1 Pad
Word
2 Feedback
(LSW)
3 Feedback
4 Datalink
A1
5 Datalink
A1
6 Datalink
A2
7 Datalink
A2
8 Datalink
B1
9 Datalink
B1
1 Datalink
B2
1 Datalink
B2
1 Datalink
C1
1 Datalink
C1
1 Datalink
C2
1 Datalink
C2
1 Datalink
D1
1 Datalink
D1
1 Datalink
D21
P155
1
Logic Status
P72
Speed Ref DPI
P724 Data Out A1
P725 Data Out A1
P726 Data Out A2
P727 Data Out A2
P728 Data Out B1
P729 Data Out B1
P730 Data Out B2
P731 Data Out B2
P732 Data Out C1
P733 Data Out C1
P734 Data Out C2
P735 Data Out C2
P736 Data Out D1
P737 Data Out D1
P738 Data Out D2
P739 Data Out D2
CIP Generic Message
Source and Destination
Tags
Message
Buffer
Message
Handler
2
DPI
DeviceNet