Cable, control, Cable, motor lengths, Cable, power – Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual
Page 24: Cable trays and conduit

24
Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013
Chapter 1
Detail Drive Configuration and Operation
Parameter 418 [Brake TP Sel] selects a value to monitor for diagnostics of the
dynamic brake protection. Possible selections for parameter 418 [Brake TP Sel]
are:
Parameter 419 [Brake TP Data] displays the data selected in parameter 418
[Brake TP Sel].
Cable, Control
See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives, publication
Cable, Motor Lengths
See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives, publication
Cable, Power
See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives, publication
Cable Trays and Conduit
See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives, publication
Parameter 418 [Brake TP Sel]
Setting
Description
0 - “Zero”
Do not monitor any test point for the brake protection.
1 - “Duty Cycle”
Actual duty cycle of the dynamic brake IGBT where a value of 0 in parameter 419
[Brake TP Data] = full open and 1 = full on.
2 - “Power Actual”
Actual power applied to the resistor (Watts).
3 - “Max BodyTemp”
Maximum temperature that the resistor body can handle (°C).
4 - “Max ElemTemp Act”
Maximum temperature that the resistor element can handle (°C).
5 - “BodyTemp Act”
Predicted temperature of the resistor body (°C).
6 - “ElemTemp Act”
Predicted temperature of the resistor element (°C).
7 - “BTmpTrip Stat”
Maximum resistor body temperature has been exceeded when parameter 419
[Brake TP Data] = 1.
8 - “ETmpTripStat”
Maximum resistor element temperature has been exceeded when parameter 419
[Brake TP Data] = 1.
9 - “Int DB Ohms”
Rating of internal resistor when internal resistor is installed (Ohms).
10 - “Data State”
A value of 0 in parameter 419 [Brake TP Data] = initial state, 1 = internal resistor
data loaded, 2 = external resistor data loaded.
11 - “MC BrakeEnbl”
A value of 0 in parameter 419 [Brake TP Data] = dynamic braking disabled, 1 =
dynamic braking enabled.
12 - “1/rdb”
Inverse of the resistance (1/Ohms).
13 - “1/th_eb”
Inverse of the thermal impedance from the resistor element to body (Watts/°C).
14 - “1/ce”
Inverse of the resistor element thermal mass (°C/W*s).
15 - “tamax”
Maximum ambient temperature of resistor (°C).
16 - “1/th_ba”
Inverse of the thermal impedance from the resistor body to element (Watts/°C).
17 - “1/cb”
Inverse of the resistor body thermal mass (°C/W*s).
18 - “DB IGBT Amp”