Jog reference, Stop command, Direction control and bipolar reference – Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual
Page 133: Speed limits

Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013
133
Detail Drive Configuration and Operation
Chapter 1
Jog Reference
Two separate jog speeds can be used as a speed reference - parameter 17 [ Jog
Speed 1] or 18 [ Jog Speed 2]. For more information on jog speeds see
.
Stop Command
When a stop command is issued, parameter 157 [Logic Ctrl State] bit 0 - “Spd
Ref En” is set to 0, causing a zero speed to be selected. When [Logic Ctrl State]
bit 0 is set to 1, the selected speed or jog reference is used.
Direction Control and Bipolar Reference
The direction of rotation of the motor can be controlled by a forward/reverse
command or by the use of a bipolar signal. For more information on direction
control, see Direction Control and Bipolar Reference on page
Speed Limits
The next section sets the forward and reverse speed limits for the speed reference.
Parameter 31 [Fwd Speed Limit] sets the positive speed limit, in RPM. Parameter
30 [Rev Speed Limit] sets the negative speed limit, in RPM. Parameter 41
[Limited Spd Ref ] contains value, in RPM, of the limited speed reference.
1
0
157
00
0
Logic Ctrl State
30
31
Limit
41
Rev Speed Limit
Fwd Speed Limit
Limited Spd Ref