Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual
Page 44
![background image](/manuals/581366/44/background.png)
44
Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013
Chapter 1
Detail Drive Configuration and Operation
[DigIn 2 Sel] can be set to the following values:
[DigIn 3 Sel] can be set to the following values:
[DigIn x Debounce] sets a delay time to allow any bounce in the digital input to
settle out. This parameter has a range of 0 to 15.5 milliseconds.
When [DigIn x Sel] is set to “User Select,” the function of the digital input is
determined by the following:
•
[DigIn x Data] determines any bits that should be permanently set. [DigIn
x Data] sets the value of [DigIn x User Data] except for the bit chose in
[DigIn x Bit]
•
[DigIn x Data] determines the bit you wish to toggle based on whether the
digital input is on or off
Value
Description
Value
Description
0
“Not Used”
14
“Normal Stop”
1
“Enable”
15
“Spd Ref Sel1”
2
“Clear Faults”
16
“Spd Ref Sel2”
3
“Ext Fault”
17
“Spd Ref Sel3”
4
“Norm Stop-CF”
18
“CurLim Stop”
5
“Start”
19
“Coast Stop”
6
“Reverse”
21
“BscIndx Step”
7
“Run”
22
“BscIndxStpRv”
8
“Fwd/Reverse”
26
“PI Trim En”
9
“CurLim Stop”
29
“Trend Trig”
10
“Jog 1”
30
“PreCharge En”
11
“Aux Fault”
31
“Regis 1 Ltch”
12
“AuxFault Inv”
32
“+Hrd OvrTrvl”
13
“Jog 2”
33
“-Hrd OvrTrvl”
Value
Description
Value
Description
0
“Not Used”
9
“CurLim Stop”
1
“Normal Stop”
10
“Coast Stop”
2
“Start”
11
“Aux Fault”
3
“Run”
12
“AuxFault Inv”
4
“Clear Faults”
13
“User Select”
5
“Stop-CF”
23
“Logix Motion”
6
“Jog 1”
24
“+Hrd OvrTrvl”
7
“Jog 2”
25
“-Hrd OvrTrvl”
8
“Fwd/Reverse”