beautypg.com

B - dtam micro cable diagrams, Dtam micro cable diagrams, Dtam micro cables – Rockwell Automation 2707-M232P3_M485P3 DTAM Micro Operator Interface Module User Manual

Page 91: Appendix

background image

A–B

B

Appendix

B–1

DTAM Micro Cable Diagrams

Catalog No. 2707-NC1

Use the RS-485 Network Interface Cable to connect the RS-485 version of
the DTAM Micro (Catalog No. 2707-M485P3) to an SLC network.

DTAM Micro RS-485

Communication Port

SLC 500 Programming Port or

Isolated Link Coupler Peripheral Port

8-Pin Male RJ Connector

AMP#5-55179-X

9-Pin Male D Connector

1

2

3

4

5

6

7

8

9

1

2

3

4

5

6

7

8

Data Out –

Data Out +

Data In –

Data In +

Transmit Enable

Ground

Shield

Data (CH A)

Data (CH B)

24 VDC

Gnd RS-485

Transmit Enable TX–EN
Shield

Gnd RS-485

24 VDC

Catalog No. 2707-NC2

Use the Upload/Download Cable to connect the RS-232 version of the
DTAM Micro (Catalog No. 2707-M232P3) to a personal computer for
transferring applications. A 25– to 9–pin adapter may be required if your
computer has a 25–pin communication port.

DTAM Micro RS-232

Communications Port

Data In

Data Out

Signal Ground

Data In

Data Out

Signal Ground

1

2

3

4

5

1

2

3

4

5

Computer 9 Pin

Serial Port (COM1, COM2)

9-Pin Male D Connector

9-Pin Male D Connector

DTAM Micro Cables