Special Controller Functions

Appendix C

DTAM Micro

C–5

To read/write the contents of controller Bit and Integer files:

1. Select item 1 from the Special Menu to access the P–A/D function.

You are prompted for a file type:

Select File Type:
(O) Output

2. Press [NEXT] and [PREV] keys to scroll through the file types.

Select either Binary or Integer and press [

].

You are prompted for a file number:

Select File Num=_____

3. Enter the file number (3-999 for PLCs or 3-7, 9-255 for SLCs) and

press [

].

You are prompted for an element number:

Select File Num=103
Elem= _____

4. Enter the element number. If you are accessing PLC-5 data, you must

enter an octal value.

You are shown the decimal value of the data:

File=N103

DEC

Elem=10

19774

Data Format

Data

Initially, you are shown a decimal value for the status. If you press
[NEXT], the hexadecimal format is displayed:

File=N103

HEX

Elem=10

4D3E

Pressing [NEXT] again displays the binary value:

File=N103

Elem=10

0011111001001101

5. To change a value, move the cursor into the data field using the [NEXT]

or [PREV] keys. Enter the new data. If you are editing binary data, use
the [+/-] key to toggle the data between 1 and 0.

6. Press [

] to to load the new data into the file element.

7. To exit, press the [MODE] key to return to the initial P-A/D screen.

You can press the [MODE] key at any time during the P-A/D function.

8. Pressing the [MENU] key at the P-A/D screen exits the P-A/D function

and displays the Main Menu.

Reading / Writing Controller
Bit and Integer Files