Chapter 8

Troubleshooting and Maintenance

8–12

Only available on the RS-485 version. Use the TXEN test to verify the
transmit enable line at the RS-485 communications port.

The TXEN test requires a loopback connector with an LED. You can
construct a simple loopback connector as shown below:

DB9 Female

1

Data Out –

2

Data Out +

3

Data In -

4

Data In +

5

Signal Ground

6

Transmit Enable

7

Not Used

8

Signal Ground

9

Shield

Pin Signal Name

RS-485 Port Only

Connects pins 1

!3

and pins 2

! 4

LED and 750

W resistor

between pins 2-4 and 6

Loopback Connector

750

W

LED

To test the transmit enable line:

1. Use the [NEXT] and [PREV] keys to display TXEN Test on the

test selection screen.

DTAM Micro Diag Test

TXEN Test

2. Press [

] to initiate the test.

The LED should flash at approximately 1 second intervals indicating that
the transmit enable line is functioning properly.

3. Pressing [

] terminates the TXEN test.

The next test selection screen is displayed.

DTAM Micro Diag Test

Reset DUT

4. To terminate the test function , press the [NEXT] and [PREV] keys to

display Reset DUT in the test selection area. Press [

] to reset the

terminal.

TXEN Test