The 6 position DIP switch allows you to enable or disable certain functions.
The DIP switch is accessed by removing the access cover on the back (access
cover is shipped in the hardware bag on new units).

Figure 2.4
DIP Switch

1

2

3

4

5

6

Back of DTAM Micro

OPEN

ON =

Side View

Switch Position

Setting

Function

1➀

ON

ON position allows the transfer of application files between
the DTAM Micro and personal computer running DPS. All
communication between the DTAM Micro and controller are
disabled. Keypad entry is also disabled.

OFF

OFF enables communication between the DTAM Micro and
controller.

ON

ON enables the master code. Enabling the master code
allows any security code to be accessed or modified.

2

OFF

OFF disables the master code. Disabling the master code
still allows access to a security screen or special functions
but does not allow security codes to be modified.

ON

ON enables the Mode key on the front panel.

3

OFF

OFF disables the Mode key on the front panel.

4, 5, 6

ON or OFF

Reserved for future use.

➀ DTAM Micro is reset each time this switch position is changed.