Connections and Setup

Chapter 7

Communication

7–2

The RS-232 port of the DTAM Micro terminal (Catalog No. 2707-M232P3)
allows point-to-point communications with:

PLC-5 Channel 0 (configured as RS-232 port)

SLC 5/03, 5/04, 5/05 RS-232 port

MicroLogix 1000

The figure below shows typical RS-232 connections.

DTAM Micro to PLC-5 Channel 0

RS-232

DTAM Micro Terminal

PLC-5

Cable (Catalog No. 2707-NC3)

DTAM Micro
RS-232 Port

Channel 0

Catalog No. 2707-M232P3

DTAM Micro to SLC 5/03

RS-232

Channel 0

SLC 5/03

Cable (Catalog No. 1747-CP3)

DTAM Micro Terminal

DTAM Micro
RS-232 Port

Catalog No. 2707-M232P3

Gender Adapter

To connect the DTAM Micro to an RS-232 device:

1. Make sure that the DTAM Micro is not connected to a voltage source.

2. Use the proper cabling to connect the DTAM Micro communications port

to the port of the controller (PLC-5 channel 0 or SLC 5/03, SLC 5/04
RS-232 port).

Use cable, Catalog No 2707-NC3 for PLC-5 channel 0 connection.

Use cable, Catalog No. 1747-CP3 for SLC 5/03, SLC 5/04 or 5/05 port
connection.
This cable requires a 9-pin female to male gender adapter.

If you need to make your own cable, refer to the cable diagrams in
Appendix B. The maximum recommended cable length is 50 feet
(15.2 meters).

3. Make sure that the communication parameters of the DTAM Micro

terminal match the host device.

4. Apply power and verify that communications are established.

Connecting