Get device info block 4 message – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual
Page 98
![background image](/manuals/580752/98/background.png)
Publication 1794-UM065B-EN-E - September 2010
86 Configure Module Messaging
Get Device Info Block 4 Message
9
SVUnits
(1 byte)
CMD#3, Byte 9; Set to 0 if
device does not return a
value for SV.
10
TVUnits
(1 byte)
CMD#3, Byte 14; Set to 0 if
device does not return a
value for TV.
11
FVUnits
(1 byte)
CMD#3, Byte 19; Set to 0 if
device does not return a
value for FV.
12
PVRangeUnits
(1 byte)
CMD#15, Byte 2
13
Pad_8 alignment
(1 byte)
14
HARTPreamble
(1 byte)
CMD#0, Byte 3
15
HARTFlages
(1 byte)
CMD#0, Byte 8
(1)
Data in offsets 4…15 will be set to 0 if Status in offset 0 indicates a problem (Status = 0x86 or 0x87).
Get Device Information Block 4 Message – Request Packet Structure
Field
Value
Definition
Message Type
"CIP Generic"
Service Type
Get Attribute Single
Read From Module
Service Code
0x0E
Class Name
0x7D
FLEX Module Object
Instance
1…8 (Module next to Adapter = 1)
Module Location
Object Attribute
0x8A = Channel 0 (Add 4 for next channel)
0x8E = Channel 1
0x92 = Channel 2
0x96 = Channel 3
0x9A = Channel 4
0x9E = Channel 5
0xA2 = Channel 6
0xA6 = Channel 7
Selects Channel that the
data is from
Reply Size
38 bytes
Request Size
0
Get Device Information Block 3 Message – Reply Packet Structure
Offset
(1)
Field
Value
Definition