Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual
Page 52
Publication 1794-UM065B-EN-E - September 2010
40 1794-IF8IH and 1794-OF8IH Configuration
Alarms are adjustable with Formats 0-7. See Data Formats and Error Ranges.
Alarms are preset/fixed with Formats 8-15. See Data Formats and Error
Ranges.
Range: 0…15, See 1794-IF8IH Data Formats on page 40
Default: 0
Data Table Reference: data format, Configuration Words 2 and 3, bits 0…3,
4…7, 8…11, 12…15.
1794-IF8IH Data Formats
Data
Format
Format
Resolution
Input Range
Module Data Processing
Data Table Value
(Interpretation)
Count per mA/
Resolution
0
0…20 mA
as mA
0.1% of
0…20 mA
0…22 mA
Datatable = 1000 (input)
0…22000
(0…22.000 mA)
1000/
1.0 µA
1
0…20 mA
as %
0.2% of
0…20 mA
0…22 mA
0…11000
(0…110.00%)
500/2.0 µA
2
Not Assigned
3
0…20 mA
as unsigned
integer
0.03% of
0…20 mA
0…20 mA
0…65535
(0…20 mA)
3276/
0.3052 µA
4
4…20 mA
as mA
0.1% of
4…20 mA
2…22 mA
Datatable = 1000 (input)
2000…22000
(2.000…22.000
mA)
1000/
1.0 µA
Datatable = 10000
input
(
20
)
Datatable = 65535
input
(
20
)