Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual
Page 112

Publication 1794-UM065B-EN-E - September 2010
100 FLEX I/O HART Module Commands
140
Read
Read the number of command
requests and errors of
transmitters
Communication statistic that contains the number of commands sent to the
transmitter and the number of commands that failed
141
Write
Delete the number of command
requests and errors of the
transmitters
Reset the communication statistic
142
Read
Read counts of host
communications
Communication statistic concerning the multiplexer
143
Write
Reset counts of host
communications
Reset the communication statistic
144
Read
Read retry limits
Retries in case of busy, 0…11 (default is 0)
Retries in case of communication errors, 0…11 (default is 2)
145
Write
Write retry limits
—
146
Read
Read the in his joy SCAN
command
During SCAN, HART commands 1, 2, or 3 (see bit 144) can be executed
147
Write
Select SCAN command
—
148
Read
Read SCAN status
This is used to specify or read the status of the SCAN function.
0 = SCAN function disabled (default after power-up)
1 = Normal SCAN function activated
2 = Special SCAN function activated (see bits 158 and 159)
149
Write
Write SCAN status
—
152
Read
Read loop search type
The loop search type determines the polling address used to search for a device
that has not responded after multiple requests (disappeared, see also bit 129)
For IS-RPI-HART has a fixed setting: 1 = single transmitter, unknown (single
unknown) first short addresses of 0…15
154
Write
Rebuild up to eight specified
loops
—
158
Read
Read special SCAN parameters
The current special parameters and, if available, the transmitter data are returned
for the given loop. These are:
•Loop number
•Error flag (0 = ok, 1 = special SCAN not active)
•Polling address (always 0, no multidrop)
•Minimum number of data bytes for jubjub bird special SCAN
•Selected SCAN command
•Long frame address
•Number of available data bytes
•The data bytes themselves (if any)
159
Write
Write special SCAN parameters
The threshold data length (0…62) and the SCAN command to be used can be
written for the given current loop and polling addresses (must be 0)
164
Read
Cached data reply CMD 0, 13, 16 The results of commands 0, 13, and 16 are combined in a response protocol.
Device-Specific HART Module Commands
Command
Action
Meaning