Response from the hart command – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual
Page 128
![background image](/manuals/580752/128/background.png)
Publication 1794-UM065B-EN-E - September 2010
116 FLEX I/O HART Modules Network Messaging
Response from the HART Command
The six header bytes are added in the front of the HART message response
while the remaining format is unchanged. These six bytes contain the
following information:
• Response Source
• Next Assembly
Pointer to assembly for next access.
• Channel
The actual channel to which actual contents are related.
• Handle
This indicates the Handle of the response.
Status
(6 Bytes)
Start
Character
Address
Command
Byte Count
(Response
Code)
Data
Checksum
Byte
0
1
2
3
4
5
Bit
0…2
3…7
0…7
0…7
0…7
0…3
4
5
6
7
0
1
2…7
Resp
Source
Next assy index
Ch
Handle
Resp
Error
Assy
Access
Error
Chain
Data
Req
allow
Loop
status
avail
Lock
Cold
Start
Res
Value
Meaning
0
Not valid (default)
1
Source is HART response
2
Source is Scan data
3
CMD 48 response
4…7
Reserved
Value
Meaning
0…7
Channel of I/O module
0x20
FLEX I/O HART module itself