Local fault mode – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual
Page 22

Publication 1794-UM065B-EN-E - September 2010
10 Configurable FLEX I/O Analog Module Features
Select Your Analog Output
Module Operating Features
All features of the 1794-OF8IH analog output module are independently
configurable.
Local Fault Mode
The Local Fault Mode can be programmed to determine how the module
responds to communications faults and internal module faults.
When setting the Local Fault Mode feature in your programming software, set
this feature’s bit to 0 to use the analog fault state or digital fault state only if a
communications fault occurs. Set the bit to 1 to use the Analog Fault state or
Digital Fault state if any fault occurs.
7
4…20 mA
as unsigned
integer
0.03% of
4…20 mA
0…65535
(4…20 mA)
4095
With
error
steps
8
Not assigned
9
10
11
0…20 mA
as A/D
count
0.04% of
0…20 mA
0…22 mA
0…55000
(0…22 mA)
2500
All
fixed
12
4…20 mA
as %
0.16% of
4…20 mA
3.6…21 mA
-250 … +10625
(2’s complement)
(-2.50…+106.25%)
625
NAMU
R NE 4
all fixed
13
4…20mA
as %
0.16% of
4…20 mA
3…21 mA
-625 … +10625
(2’s complement)
(-6.25…+106.25%)
All
fixed
14
4…20 mA
as %
0.16% of
4…20 mA
2…22 mA
-1250 … +11250
(2’s complement)
(-12.50…+112.50
%)
15
Not assigned
1794-IF8IH Data Formats
Data
Format
Format
Resolution
Input
Range
Module Data Processing
Data Table Value
(Interpretation)
Count
per mA
Error
Steps
input-4
(
16
)
Datatable = 65535
input
(
22
)
Datatable = 55000
input-4
(
16
)
Datatable = 10000
input-4
(
16
)
Datatable = 10000
input-4
(
16
)
Datatable = 10000
IMPORTANT
The default selection value for all parameters is 0.