Real time data (rtd) profile, status parameters – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual
Page 82
Publication 1794-UM065B-EN-E - September 2010
70 1794-IF8IH and 1794-OF8IH Configuration
changes the appropriate channel's Assembly 125 entry from 0xC0 Cyclic EDT
Get to 0x80 EDT Get or 0x40 Cyclic EDT Set to 0x00 EDT Set.
Whenever the adapter receives a ForwardOpen to an EDT module, the
adapter automatically rereads the module's Assembly 125 to gain a new view of
the assemblies. This reread is to check for any changes of CEDT Assemby
status to EDT status. If a CMD3 Disable Chx is received on any particular
channel, now the previous CEDT assembly is marked as an EDT assembly
and the adapter does not add that assembly to the CEDT scan. This
ForwardOpen reread happens any time a module receives a ForwardOpen,
including a Null-ForwardOpen received during system runtime.
Range: 0=Enabled, 1=Disabled
Default: 0
Real Time Data (RTD)
Profile, Status Parameters
1794-OF8IH Primary Data Table
Word/S
ISOC
Read/
Write
Data
Transport
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0/MSW Read
RealT
Bus Fail Bits
#
# Words to Read
Module ID/Type
1/EDT
Read
RealT
PU/
Cfg
Event
Pdg
Reserved
Read Write SeqCount
EDT Data Byte from Module
2/S0
Read
RealT
F7
F6
F5
F4
F3
F2
F1
F0
Diagnostic status
3/S1
Read
RealT
Reserved
4/S2
Read
RealT
C7
C6
C5
C4‘
C3
C2
C1
C0
Reserved
5/S3
Read
RealT
X7
X6
X5
X4
X3
X2
X1
X0
Reserved
6/EDT
Write
RealT
Prog
/Run
Fault
Reserved
Read Write SeqCount
EDT Data Byte from Module
7/O0
Read
RealT
Rese
rved
Globa
l
reset
Reservd
D7
D6
D5
D4
D3
D2
D1
D0
8/O1
Write
RealT
Output Data Channel 0
9/O2
Read
RealT
Output Data Channel 1
10/O3
Read
RealT
Output Data Channel 2
11/O4
Read
RealT
Output Data Channel 3
12/O5
Read
RealT
Output Data Channel 4
13/O6
Read
RealT
Output Data Channel 5