Fault alarm (8 of 1 bit each), Diagnostic data (1 of 8 bits) – Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual
Page 83
Publication 1794-UM065B-EN-E - September 2010
1794-IF8IH and 1794-OF8IH Configuration 71
Fault Alarm (8 of 1 bit each)
Alarm signal for open wire channel fault, detected at <2 mA (<500 µA in
digital mode) and short circuit (R<42 in the 4…20 mA range, <86 in digital
mode, channel off).
This alarm is disabled when a data format is selected which includes 0 mA.
Range: 0=Normal, 1=Wire off/short circuit fault detected
Default: 0
Diagnostic Data (1 of 8 bits)
Response from module as to its condition.
14/O7
Read
RealT
Output Data Channel 6
15/EDT
Read
RealT
Output Data Channel 7
Where:
Fn : Channel n Fault alarm
Cn : Channel n HART Current Fault
Xn : HART Transmitter List
Dn : Channel n Digital out
1794-OF8IH Primary Data Table
Word/S
ISOC
Read/
Write
Data
Transport
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Diagnostic Status Value: 0
Channel
Failure
0x00
All
No Errors (default)
0x10
Channel 0
HART Iloop Threshold Configuration Error
0x11
Channel 1
HART Iloop Threshold Configuration Error
0x12
Channel 2
HART Iloop Threshold Configuration Error
0x13
Channel 3
HART Iloop Threshold Configuration Error
0x14
Channel 4
HART Iloop Threshold Configuration Error
0x15
Channel 5
HART Iloop Threshold Configuration Error
0x16
Channel 6
HART Iloop Threshold Configuration Error
0x17
Channel 7
HART Iloop Threshold Configuration Error
0x40
Channel 0
Format Configuration Error
0x41
Channel 1
Format Configuration Error
0x42
Channel 2
Format Configuration Error
0x43
Channel 3
Format Configuration Error