14 Configurable FLEX I/O Analog Module Features
Not all 16 words need be allocated. The 1794-IF8IH has the following RTD
I/O Profile:
Chapter Summary
In this chapter, we told you about the FLEX I/O system and the analog I/O
modules, and how they communicate with programmable controllers. Move
on to the next chapter to learn how to install your FLEX I/O analog module.
1794-IF8IH RTD I/O Profile
RTD Index
Assembly Index
Assembly
RTD 0
MSW
Module Status Word
RTD 1
EDT Read Word
EDT Read Word
RTD 2…9
I:0…I:7
RTD Input Data
1794-IF8IH Analog data table
Word
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Channel 0 Input Data
1
Channel 1 Input Data
2
Channel 2 Input Data
3
Channel 3 Input Data
4
Channel 4 Input Data
5
Channel 5 Input Data
6
Channel 6 Input Data
7
Channel 7 Input Data
8
H7
H6
H5
H4
H3
H2
H1
H0
L7
L6
L5
L4
L3
L2
L1
L0
9
R7
R6
R5
R4
R3
R2
R1
R0
P7
P6
P5
P4
P3
P2
P1
P0
10
Reserved
Diagnostic Status
11
C7
C6
C5
C4
C3
C2
C1
C0
F7
F6
F5
F4
F3
F2
F1
F0
12
X7
X6
X5
X4
X3
X2
X1
X0
Reserved
Where:
Hn: Channel n High Alarm
Ln: Channel n Low Alarm
Pn: Channel n Out Of Range Alarm
Rn: Channel n Second (Remote) Alarm
Fn: Channel n HART Failure
Cn: Channel n HART Current Fault
Xn: Channel n HART Transmitter Present
0: False 1: True