Rockwell Automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Modules User Manual
Page 78

Publication 1794-UM065B-EN-E - September 2010
66 1794-IF8IH and 1794-OF8IH Configuration
Range: 0…15. Refer to the 1794-OF8IH Data Formats table.
If data is sent to the module which is out of range, the value is clipped and
Diagnostic Data is set to "11" data out of range. To view a graphical
representation of this performance, see the example on page 12.
1794-OF8IH Data Formats
Data
Format
Format
Resolution Full
Output
Range
Module Data Processing
Data Table Value
(Interpretation)
Count per
mA/
Resolution
Analog Fault
State
0 (default) mA as
0…20 mA
0.1% of
0…20 mA
0…22 mA
0…22000
(0…22.000 mA)
1000/
1.0
µA
Min=0 mA
Max=22 mA
hold
Last=hold
FS value
1
% as
0…20 mA
0.2% of
0…20 mA
0…22 mA
0…11000
(0…110.00%)
500/
2.0
µA
Min=0 mA
Max=22 mA
hold
Last=hold
FS value
2
0…20 mA
—
0…22 mA Not Assigned
3
Unsigned
integer as
0…20 mA
0.03% of
0…20 mA
0…20 mA
0…65535
(0…20 mA)
3276/
0.305
µA
Min=0 mA
Max=20 mA
hold
Last=hold
FS value
4
mA as
4…20 mA
0.1% of
4…20 mA
2…22 mA
2000…22000
(2.000…22.000
mA)
1000/
1.0
µA
Min=2 mA
Max=22 mA
hold
Last=hold
FS value
5
4…20 mA
—
4…20 mA Not assigned
6
4…20 mA
4…20 mA Not assigned
7
Unsigned
integer as
4…20 mA
0.03% of
4…20 mA
4…20 mA
0…65535
(4…20 mA)
4095/
0.244
µA
Min=4 mA
Max=20 mA
hold
Last=hold
FS value
8
0…20 mA
0…20 mA Not assigned
9
0…20 mA
0…20 mA Not assigned
10
0…20 mA
0…20 mA Not assigned
11
0…20 mA
0…20 mA Not assigned
12
4…20 mA
Not assigned
13
4…20 mA
Not assigned
14
% as
4…20 mA
0.16% of
4…20 mA
2…22 mA
-1250 … +11250
(2’s complement)
(-12.50% …
+112.50%)
625/
1.6
µA
Min=2 mA
Max=22 mA
hold
Last=hold
FS value
15
4…20 mA
4…20 mA Not assigned
Output =
datatable
(
1000
)
Output = 20
datatable
(
10000
)
Output = 20
datatable
(
65535
)
Output =
datatable
(
1000
)
Output = 16
datatable
(
65535
)
+ 4
Output = 16
datatable
(
10000
)
+ 4