Use the 1794-OF8IH Module with the Generic Profile 137
Analog Fault Mode
4
(2)
0
1
0
0
4…20 mA in Milliamps
2.00
22.00
2000
(2.000 mA)
22000
(22.000 mA)
1.0 µA
7
(2)
0
1
1
1
4…20 mA in UINT
4.00
20.00
0
65535
0.2441 µA
14
(2)
1
1
1
0
4…20 mA in % Full Scale
2.00
22.00
-1250
(-12.50%)
11250
(112.50%)
1.6 µA
(1)
All other formats are invalid.
(2)
HART Communications supported with these data formats only.
Channel Data Formats
Format
(1)
Bits
Format Name
Signal Range
User Range
Resolution
15 14 13 12
11 10 9
8
7
6
5
4
LO
HI
LO
HI
3
2
1
0
Channel
Bits
0
[Adapter Name]:[Slot]:C.Data[4].0
[Adapter Name]:[Slot]:C.Data[4].1
1
[Adapter Name]:[Slot]:C.Data[4].8
[Adapter Name]:[Slot]:C.Data[4].9
2
[Adapter Name]:[Slot]:C.Data[5].0
[Adapter Name]:[Slot]:C.Data[5].1
3
[Adapter Name]:[Slot]:C.Data[5].8
[Adapter Name]:[Slot]:C.Data[5].9
4
[Adapter Name]:[Slot]:C.Data[6].0
[Adapter Name]:[Slot]:C.Data[6].1
5
[Adapter Name]:[Slot]:C.Data[6].8
[Adapter Name]:[Slot]:C.Data[6].9
6
[Adapter Name]:[Slot]:C.Data[7].0
[Adapter Name]:[Slot]:C.Data[7].1
7
[Adapter Name]:[Slot]:C.Data[7].8