beautypg.com

Index abort deceleration, Index abort deceleration -50 – Rockwell Automation 2098-DSD-xxx Ultra3000 Host Commands for Serial Interface User Manual

Page 66

background image

Publication 2098-RM003A-EN-P October 2001

2-50

Command Reference

Index Abort Deceleration

Format:

:aa0B9fddddddddcc

Parameter
Code:

0x0B9

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dddddddd

Deceleration to be used if the stop index input is
activated, in units of counts/second/second.

Minimum
Value:

0x00000000

Maximum
Value:

0x7FFFFFFF

Default:

100,000