Analog operating mode commands, Analog position scale, Analog position offset – Rockwell Automation 2098-DSD-xxx Ultra3000 Host Commands for Serial Interface User Manual
Page 36: Analog operating mode commands -20, Analog position scale analog position offset
Publication 2098-RM003A-EN-P October 2001
2-20
Command Reference
Analog Operating Mode
Commands
Analog Position Scale
Analog Position Offset
Format:
:aa028fddcc
Parameter
Code:
0x028
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x08 = Invalid Function Code
Data Fields:
dddd
Analog position scale, in units of counts/Volt.
Minimum
Value:
0x8001
Maximum
Value:
0x7FFF
Default:
1000
Format:
:aa029fddddcc
Parameter
Code:
0x029
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields:
dddd
Analog position offset, in units of milliVolts.
Minimum
Value:
-10000
Maximum
Value:
10000
Default:
0