beautypg.com

Velocity loop i gain, Velocity loop d gain, Velocity loop i gain -88 velocity loop d gain -88 – Rockwell Automation 2098-DSD-xxx Ultra3000 Host Commands for Serial Interface User Manual

Page 104: Velocity loop i gain velocity loop d gain

background image

Publication 2098-RM003A-EN-P October 2001

2-88

Command Reference

Velocity Loop I Gain

Velocity Loop D Gain

Format:

:aa020fddddcc

Parameter
Code:

0x020

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dddd

Minimum
Value:

0

Maximum
Value:

4000

Default:

66

Format:

:aa021fddddcc

Parameter
Code:

0x021

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dddd

Minimum
Value:

-1000

Maximum
Value:

1000

Default:

0