Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual
Page 97
Publication 1794-UM063A-EN-P - March 2006
FLEX I/O HART Module Commands B-5
141
Write
Delete the number of command
requests and errors of the
transmitters
Reset the communication statistic
142
Read
Read counts of host
communications
Communication statistic
concerning the multiplexer
143
Write
Reset counts of host
communications
Reset the communication statistic
144
Read
Read retry limits
Retries in case of busy, 0…11
(default is 0)
Retries in case of communication
errors, 0…11 (default is 2)
145
Write
Write retry limits
—
146
Read
Read the in his joy SCAN
command
During SCAN, HART commands 1,
2, or 3 (see bit 144) can be
executed
147
Write
Select SCAN command
—
148
Read
Read SCAN status
This is used to specify or read the
status of the SCAN function.
0 = SCAN function disabled
(default after power-up)
1 = Normal SCAN function
activated
2 = Special SCAN function
activated (see bits 158 and 159)
149
Write
Write SCAN status
—
152
Read
Read loop search type
The loop search type determines
the polling address used to search
for a device that has not
responded after multiple requests
(disappeared, see also bit 129)
For IS-RPI-HART has a fixed
setting: 1 = single transmitter,
unknown (single unknown) first
short addresses of 0…15
154
Write
Rebuild up to eight specified
loops
—
Table B.3 Device-Specific HART Module Commands
Command
Action
Meaning