beautypg.com

Chapter summary, Chapter summary -21 – Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual

Page 45

background image

Publication 1794-UM063A-EN-P - March 2006

Configurable FLEX I/O Analog Module Features 2-21

HART Read Back Threshold

This bit delivers the percentage value, in steps of 1%, of the threshold for
forcing the HART read back indication. The maximum input signal deviation
for HART analog modules is 31%.

If there is no HART transmitter on the loop or if the loop is not in the
transmitter list, the function is switched off internally in the I/O module.
The values are:

• 0 = disable indicator (default)
• 1 to 4 = not supported from the I/O module (set to 5 internally)
• 5 to 31 = percentage threshold data (5 to 31%)

Chapter Summary

In this chapter, we told you about the FLEX I/O system and the analog I/O
modules, and how they communicate with programmable controllers. Move to
Chapter 3 to learn how to install your FLEX I/O analog module.

This manual is related to the following products: