beautypg.com

Appendix b, Flex i/o hart module commands, What this appendix contains – Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual

Page 93: Protocol overview

background image

1

Publication 1794-UM063A-EN-P - March 2006

Appendix

B

FLEX I/O HART Module Commands

What This Appendix
Contains

Read this appendix to learn the module commands to and from FLEX I/O
HART modules.

Protocol Overview

HART field communications protocol is widely accepted in the industry as the
standard for digitally enhanced 4 to 20 mA communication with smart field
instruments. The HART protocol message structure, command set, and status
are discussed in this appendix.

The HART command set is organized into three groups and provides
read/write access to a wide array of information available in smart field
instruments:

• Universal commands provide access to information that is useful in

normal plant operation such as the instrument manufacturer, model,
tag, serial number, descriptor, range limits, and process variables. All
HART devices must implement universal commands.

• Common practice commands provide access to functions, which can be

carried out by many devices though, not all.

• Device-specific commands provide access to functions that may be

unique to a particular device.