Common practice commands – Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual
Page 107
Publication 1794-UM063A-EN-P - March 2006
Additional HART Protocol Information C-9
Common Practice
Commands
Table C.6 Common Practice Commands
Command
Data in Command
Data in Reply
#
Function
Byte
Data
Type
(5)
Byte
Data
Type
33
Read transmitter
variables
—
None
(2)
—
0
Transmitter variable
code for slot 0
—
1
Units code for slot 0
2…5
Variable for slot 0
(F)
6
Transmitter variable
code for slot 1
—
7
Units code for slot 1
8…11
Variable for slot 1
(F)
12
Transmitter variable
code for slot 2
(6)
—
13
Units code for slot 2
14…17 Variable for slot 2
(F)
18
Transmitter variable
code for slot 3
—
19
Units code for slot 3
20…23 Variable for slot 3
(F)
34
Write damping value 0…3
Damping value
(seconds)
(F)
—
As in command
(F)
35
Write range values
0
Range units code
—
—
As in command
(F)
1…4
Upper range value
(F)
—
5…8
Lower range value
(F)
36
Set upper range
value (push SPAN
button)
—
None
—
—
None
—
37
Set lower range
value (push ZERO
button)
—
None
—
—
None
—
38
Reset configuration
changed flag
—
None
—
—
None
—
39
EEPROM control
0
(1)
EEPROM control code
—
—
As in command
—
40
Enter/edit fixed
current mode
0…3
Current (mA)
(3)
(F)
—
As in command
—
41
Perform device
self-test
—
None
—
—
None
—
42
Perform master
reset
—
None
—
—
None
—