How to Use the
HART Capabilities

Before using the HART capabilities, be sure that:

• the I/O module and the associated field device are working properly in

the analog 4 to 20 mA mode.

• the I/O module is configured for 4 to 20 mA range.
• the field device is HART capable.
• no more than one HART field device is connected to each channel.
• input filtering is set to a valid (defined) value.

HART Implementation
Overview

The FLEX I/O HART modules act as intelligent HART multiplexers.
Basically, the module learns which HART devices are attached to its channels
and then routes HART messages, as appropriate, between the HART field
devices and the flexbus. Since the HART modules act as intelligent HART
multiplexers, HART commands can be issued to the HART modules
themselves.

Communication on the flexbus occurs between the adapter and the HART
module. The adapter converts these messages to the appropriate network
format for communication with the controlling processor. The controlling
processor gets its command from the user program, storing the responses in
its memory.

Processor

User Program

Adapter

FLEX I/O
HART I/O
Module

HART
Field Device

Command

Response

For Example,
ControlNet

Flexbus

4 to 20 mA