Fault alarm -11, Fault alarm – Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual
Page 35
![background image](/manuals/580538/35/background.png)
Publication 1794-UM063A-EN-P - March 2006
Configurable FLEX I/O Analog Module Features 2-11
Fault Alarm
Fault Alarm selects whether the channel pair fault detection is enabled or
disabled. There is a 100 Hz (10 ms) filter for wire off or lead break detection.
Use your programming software to set the Fault Alarm. Set the feature bit
to 0 to disable the alarm. Set the bit to 1 to enable wire off/lead break
fault detection.
10
Not Assigned
11
D/A count
as 0…20
mA
0.28% of
0…20 mA
0…22 mA
0…8000
(0…22 mA)
363
Min=0 mA
Max=22 mA
Hold
last=hold
50%=11 mA
12
4…20 mA
—
—
Not assigned
—
—
—
13
% as
4…20 mA
0.16% of
4…20 mA
3…21 mA
-625 …+10625
(2’s complement)
(-6.25…+106.25
%)
625
Min=3 mA
Max=21 mA
Hold
last=hold
50%=12 mA
14
% as
4…20 mA
0.16% of
4…20 mA
2…22 mA
-1250…+11250
(2’s complement)
(-12.50…+112.5
0%)
625
Min=2 mA
Max=22 mA
Hold
last=hold
50%=12 mA
15
Not Assigned
Table 2.4 1794-OE8H Data Formats
Data
Format
Format
Resolution Full
Output
Range
Module Data Processing
Data Table Value
(Interpretation)
Count
per mA
Analog Fault
State
Output = 22
datatable
(
8000
)
Output = 16
datatable
(
10000
)
+ 4
Output = 16
datatable
(
10000
)
+ 4