Fault alarm -11, Fault alarm – Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual

Page 35

background image

Publication 1794-UM063A-EN-P - March 2006

Configurable FLEX I/O Analog Module Features 2-11

Fault Alarm

Fault Alarm selects whether the channel pair fault detection is enabled or
disabled. There is a 100 Hz (10 ms) filter for wire off or lead break detection.

Use your programming software to set the Fault Alarm. Set the feature bit
to 0 to disable the alarm. Set the bit to 1 to enable wire off/lead break
fault detection.

10

Not Assigned

11

D/A count
as 0…20
mA

0.28% of
0…20 mA

0…22 mA

0…8000
(0…22 mA)

363

Min=0 mA
Max=22 mA
Hold
last=hold
50%=11 mA

12

4…20 mA

Not assigned

13

% as
4…20 mA

0.16% of
4…20 mA

3…21 mA

-625 …+10625
(2’s complement)
(-6.25…+106.25
%)

625

Min=3 mA
Max=21 mA
Hold
last=hold
50%=12 mA

14

% as
4…20 mA

0.16% of
4…20 mA

2…22 mA

-1250…+11250
(2’s complement)
(-12.50…+112.5
0%)

625

Min=2 mA
Max=22 mA
Hold
last=hold
50%=12 mA

15

Not Assigned

Table 2.4 1794-OE8H Data Formats

Data
Format

Format

Resolution Full

Output
Range

Module Data Processing

Data Table Value
(Interpretation)

Count
per mA

Analog Fault
State

Output = 22

datatable

(

8000

)

Output = 16

datatable

(

10000

)

+ 4

Output = 16

datatable

(

10000

)

+ 4