Publication 1794-UM063A-EN-P - March 2006

5-4 Calibrate Your Module

1794-IE8H Calibration Command Byte

The Calibration command byte uses the following format to write to the
module:

The Calibration command byte uses the following format to read from the
module:

Table 5.3 1794-IE8H Calibration Command List

Calibration Command (Decimal)
Bits 0…5

Function

0

Reserved

1

Calibrate offset at 25 °C

2

Calibrate gain at 25 °C

3…7

Reserved

8

Set all calibration values to default

9

Set one specified calibration value to default

10…13

Reserved

(1)

(1)

Used during manufacture of the product. Do not use.

14

Save calibration content to EEPROM

15…63

Reserved

7

6

5

4

3

2

1

0

Calibration Command

Reserved (10

bin

Must Be Written)

7

6

5

4

3

2

1

0

Last Calibration Command Mirrored Back

Status of Last Written Calibration Command
00

bin

= Last Written Command Executed/idle

01

bin

= Error Occurred During Execution of Last

Command, Command Aborted

10

bin

= Last Written Command Pending

11

bin

= Reserved