2-10 Configurable FLEX I/O Analog Module Features

Table 2.4 1794-OE8H Data Formats

Data
Format

Format

Resolution Full

Output
Range

Module Data Processing

Data Table Value
(Interpretation)

Count
per mA

Analog Fault
State

0

mA as
0…20 mA

0.1% of
0…20 mA

0…22 mA

0…22000
(0…22.000 mA)

1000

Min=0 mA
Max=22 mA
Hold
last=hold
50%=11 mA

1

% as
0…20 mA

0.2% of
0…20 mA

0…22 mA

0…11000
(0…110.00%)

500

Min=0 mA
Max=22 mA
Hold
last=hold
50%=11 mA

2

Not Assigned

3

Unsigned
integer as
0…20 mA

0.03% of
0…20 mA

0…20 mA

0…65535
(0…22 mA)

3276

Min=0 mA
Max=20 mA
Hold
last=hold
50%=10 mA

4

mA as
4…20 mA

0.1% of
4…20 mA

2…22 mA

2000…22000
(2.000…22.000
mA)

1000

Min=2 mA
Max=22 mA
Hold
last=hold
50%=12 mA

5

4…20 mA

4…20 mA Not assigned


6

4…20 mA

4…20 mA

7

Unsigned
integer as
4…20 mA

0.03% of
4…20 mA

4…20 mA

0…65535
(4…20 mA)

4095

Min=4 mA
Max=20 mA
Hold
last=hold
50%=12 mA

8

Not Assigned

9

Output =

datatable

(

1000

)

Output = 20

datatable

(

10000

)

Output = 20

datatable

(

65535

)

Output =

datatable

(

1000

)

Output = 16

datatable

(

65535

)

+ 4