2-10 Configurable FLEX I/O Analog Module Features
Table 2.4 1794-OE8H Data Formats
Data
Format
Format
Resolution Full
Output
Range
Module Data Processing
Data Table Value
(Interpretation)
Count
per mA
Analog Fault
State
0
mA as
0…20 mA
0.1% of
0…20 mA
0…22 mA
0…22000
(0…22.000 mA)
1000
Min=0 mA
Max=22 mA
Hold
last=hold
50%=11 mA
1
% as
0…20 mA
0.2% of
0…20 mA
0…22 mA
0…11000
(0…110.00%)
500
Min=0 mA
Max=22 mA
Hold
last=hold
50%=11 mA
2
Not Assigned
3
Unsigned
integer as
0…20 mA
0.03% of
0…20 mA
0…20 mA
0…65535
(0…22 mA)
3276
Min=0 mA
Max=20 mA
Hold
last=hold
50%=10 mA
4
mA as
4…20 mA
0.1% of
4…20 mA
2…22 mA
2000…22000
(2.000…22.000
mA)
1000
Min=2 mA
Max=22 mA
Hold
last=hold
50%=12 mA
5
4…20 mA
—
4…20 mA Not assigned
—
—
—
6
4…20 mA
4…20 mA
7
Unsigned
integer as
4…20 mA
0.03% of
4…20 mA
4…20 mA
0…65535
(4…20 mA)
4095
Min=4 mA
Max=20 mA
Hold
last=hold
50%=12 mA
8
Not Assigned
9
Output =
datatable
(
1000
)
Output = 20
datatable
(
10000
)
Output = 20
datatable
(
65535
)
Output =
datatable
(
1000
)
Output = 16
datatable
(
65535
)
+ 4