Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual
Page 75
Publication 1794-UM063A-EN-P - March 2006
Calibrate Your Module 5-7
Table 5.7 1794-IE8H Interpretation of Calibration Data Structure Content During Read Access (Pending Status)
Command Byte
Item Byte
Data1
Byte
Data2
Byte
Status (Binary)
Command Bits 0…5 (Decimal)
10
Pending
1
Calibration of offset at 25 °C is in process
according to channel-mask
Channel-Mask
0
0
2
Calibration of gain at 25 °C is in process according
to channel-mask
3…7
The unknown command is trying to be interpreted
x
(2)
x
8
All calibration values are set to default
0
0
0
9
The specified calibration value is set to default
Value-identifier
10
Reserved
(1)
Reserved
Reserved
Reserved
11
Reserved
12
Reserved
13
Reserved
14
The calibration content is saved to EEPROM
x
15…61 Unknown command is mirrored back
0
0
0
62
Reserved
Reserved
Reserved
Reserved
63
Reserved
(1)
Reserved. Used during manufacture of the product. Do not use.
(2)
The received values are mirrored back.