Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual
Page 133
Publication 1794-UM063A-EN-P - March 2006
Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network F-3
Data Format Bits
3
2
1
0
Range
Resolution
Full Range
Interpretation
Data Value Table
Count per mA
7
6
5
4
0
0
0
0
0…20 mA
0.1% of 0…20 mA
0…22 mA
0…22 mA
0…22000
1000
0
0
0
1
0…20 mA
0.2% of 0…20 mA
0…22 mA
0…110%
0…11000
500
0
0
1
0
Not Valid
0
0
1
1
0…20 mA
0.3% of 0…20 mA
0…20 mA
Unsigned Integer
0…65535
3276
0
1
0
0
4…20 mA
0.1% of 4…20 mA
2…22 mA
2…22 mA
2000…22000
1000
0
1
0
1
Not Valid
Not Valid
Not Valid
Not Valid
Not Valid
Not Valid
0
1
1
0
Not Valid
Not Valid
Not Valid
Not Valid
Not Valid
Not Valid
0
1
1
1
4…20 mA
0.3% of 4…20 mA
4…20 mA
Unsigned Integer
0…65535
4095
1
0
0
0
Not Valid
1
0
0
1
Not Valid
1
0
1
0
Not Valid
1
0
1
1
0…20 mA
0.28% of 0…20 mA
0…22 mA
D/A Count
0…8000
363
1
1
0
0
Not Valid
1
1
0
1
4…20 mA
0.16% of 4…20 mA
3…21 mA
-6.25…+106.25%
-625…+10625
625
1
1
1
0
4…20 mA
0.16% of 4…20 mA
2…22 mA
-12.5…+112.5%
-1250…+11250
625
1
1
1
1
Not Valid