Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual
Page 73

Publication 1794-UM063A-EN-P - March 2006
Calibrate Your Module 5-5
Table 5.4 1794-IE8H Interpretation of Command Data Structure Content During Write Access
Command Byte
Item Byte
Data1 Byte
Data2 Byte
Reserved (Binary)
Command Bits 0…5 (Decimal)
10
(1)
1
Calibrate offset at 25 °C
Channel-Mask
Reserved
(4)
Reserved
2
Calibrate gain at 25 °C
3…7
Reserved
(2)
—
Reserved
—
8
Set all calibration values to default
Reserved
Reserved
Reserved
9
Set one specified calibration value to default
Value identifier (0)
10
Reserved
(3)
Reserved
Reserved
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Save calibration content to EEPROM
Reserved
Reserved
Reserved
15…63 Reserved
—
—
—
(1)
Always must be 10
bin
.
(2)
Do not use. Designated for future use.
(3)
Reserved. Used during manufacture of the product. Do not use.
(4)
In attempt to write this byte, write 0.