1794-oe8h calibration item byte channel-mask -17, 1794-oe8h calibration item byte channel-mask – Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual
Page 85
Publication 1794-UM063A-EN-P - March 2006
Calibrate Your Module 5-17
1794-OE8H Calibration Item Byte Channel-Mask
The Calibration item byte channel-mask uses each bit of the byte to
correspond to one channel: where 1 is calibrate this channel and 0 is do not
calibrate this channel. The LSB corresponds to channel 0, e.g., 0x03 > channel
0 and 1 have to be calibrated. Only one channel can be calibrated at a time. If
there are more channels selected within the calibration commands, the I/O
module signals an error.
Table 5.14 1794-OE8H Calibration Item Byte Value Identifier List
Identifier (Decimal)
Value
Access Rule
0
Offset channel 0
Read/write
…
…
7
Offset channel 7
8
Gain channel 0
…
…
15
Gain channel 7
16
Offset current-read-back channel 0
…
…
23
Offset current-read-back channel 7
24
Gain current-read-back channel 0
…
…
31
Gain current-read-back channel 7
32
Offset voltage-read-back channel 0
…
…
39
Offset voltage-read-back channel 7
40
Gain voltage-read-back channel 0
Read/write
…
…
47
Gain voltage-read-back channel 7
48
Status mask calibration
49
Reserved
50
Calibration day
51
Calibration month
52
Calibration year
53
Checksum over calibration values
Read
54…255
Reserved
—
7
6
5
4
3
2
1
0
Calibrate Channel 0
:
Calibrate Channel 1
Calibrate Channel 7