beautypg.com

1794-oe8h calibration item byte channel-mask -17, 1794-oe8h calibration item byte channel-mask – Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual

Page 85

background image

Publication 1794-UM063A-EN-P - March 2006

Calibrate Your Module 5-17

1794-OE8H Calibration Item Byte Channel-Mask

The Calibration item byte channel-mask uses each bit of the byte to
correspond to one channel: where 1 is calibrate this channel and 0 is do not
calibrate this channel. The LSB corresponds to channel 0, e.g., 0x03 > channel
0 and 1 have to be calibrated. Only one channel can be calibrated at a time. If
there are more channels selected within the calibration commands, the I/O
module signals an error.

Table 5.14 1794-OE8H Calibration Item Byte Value Identifier List

Identifier (Decimal)

Value

Access Rule

0

Offset channel 0

Read/write

7

Offset channel 7

8

Gain channel 0

15

Gain channel 7

16

Offset current-read-back channel 0

23

Offset current-read-back channel 7

24

Gain current-read-back channel 0

31

Gain current-read-back channel 7

32

Offset voltage-read-back channel 0

39

Offset voltage-read-back channel 7

40

Gain voltage-read-back channel 0

Read/write

47

Gain voltage-read-back channel 7

48

Status mask calibration

49

Reserved

50

Calibration day

51

Calibration month

52

Calibration year

53

Checksum over calibration values

Read

54…255

Reserved

7

6

5

4

3

2

1

0

Calibrate Channel 0

:

Calibrate Channel 1

Calibrate Channel 7