Rockwell Automation 2098-DSD-xxx Ultra3000 Digital Servo Drives with DeviceNet User Manual
Page 97

Publication 2098-RM004A-EN-P – August 2002
Programming Reference
2-81
202
Set
Electrical Cycle
Length
UINT
2
meter /
10000
Length of an electrical cycle for a linear motor
(Active if Parameter Instance 195 = 1).
Range: 100 to 10000
Default: 300
Note: Set is not allowed if the drive is enabled.
203
Set
Integral Limits
USINT
1
Indicates whether the motor provides built in
feedback for travel limits.
0 - No (default)
1 - Yes
Note: Set is not allowed if the drive is enabled.
204
Set
Rated Motor
Voltage
UINT
2
Volts
The rated voltage of the motor, in units of AC RMS
Volts.
Range: 100 to 1000
Default: 230
Note: Set is not allowed if the drive is enabled.
205
Set
Motor Resistance UINT
2
Ohms /
256
The phase to phase resistance of the motor stator.
Range: 1 to 65535
Default: 998
Note: Set is not allowed if the drive is enabled.
206
Set
Motor Inductance UINT
2
mH /
256
The phase-phase inductance of the motor stator.
Range: 1 to 65535
Default: 6144
Note: Set is not allowed if the drive is enabled.
207
Set
Flux Saturation 0
USINT
1
The motor flux saturation value at 12.5% of motor
peak current. The value is scaled so that 255
indicates no saturation, and 64 indicates 75%
saturation.
Range: 1 to 255
Default: 255
Note: Set is not allowed if the drive is enabled.
208
Set
Flux Saturation 1
USINT
1
The motor flux saturation value at 25% of motor
peak current. The value is scaled so that 255
indicates no saturation, and 64 indicates 75%
saturation.
Range: 1 to 255
Default: 255
Note: Set is not allowed if the drive is enabled.
Parameter Object,
Instances ID = 1- 1059
Parameter
Instance
Access
Rule
Parameter
Name
Data
Type
Data Size
(Bytes)
Units /
Scale
Description