4–4

Configure the Adapter for Master/Slave Communication

Publication 1794ĆUM057B-EN-P - November 2001

Condensed Format
The condensed format consists of the flags byte and the module key
parameter for each of the eight slots. This parameter dictates which
I/O module must be installed. If at any time the actual module ID
does not match this module key, the slot will be considered in fault
and the following occurs:

STATUS LED flashes red/off

an error bit in the poll response data is set

a diagnostic bit in the Ext_Diag_Data field returned in the Read
DP–Slave Diagnostic Information message response is set

All eight slots must be configured. The size for this format is always
17 bytes (including the flags byte). The condensed format structure
must be repeated for each of the eight slots.

Data format for Condensed Format

Name

Size

Description

Module Key WORD

Module ID # that must be installed

1

1

Only bits 0-12 are used. Bits 13-15 must be zero except when keying

an empty

slot where 0FFFFh is used.