4–2

Configure the Adapter for Master/Slave Communication

Publication 1794ĆUM057B-EN-P - November 2001

Send parameter data is comprised of a string of octets (1–32) that
contain 244 bytes of data:

octets 1–7 contain data specific to the:

PROFIBUS standard

defaults contained in the database (GSD) file

octets 8–32 are user configurable and contain user parameter
data
. User parameter data consists of these formats:

auto configure

condensed

full

The following illustration shows the structure of the send parameter
data table.

Group

Ident.

Ident.

Number

Minimum

Station

Delay

Watchdog

Control

Station

Status

User Parameter Data

Watchdog

Control

Octet 1

Octet 2

Octet 3

Octet 4 Octets 5&6 Octet 7

Octets 8-32

You configure these values using your

software configuration tool.

These values are defined by the PROFIBUS

standard. The defaults are provided by

the GSD file.

User Parameter Data

The first byte of the user parameter data is the flags byte. This byte
selects the appropriate format and also specifies adapter behavior.
The flags byte is defined in the following table:

Send Parameter Data Flags Byte

Bit Position

Name

Description

0-1

Format Selection 00 = Auto Configure

01 = Reserved

10 = Condensed

11 = Full

2-3

Fault Action

00 = Reset to zero

01 = Hold Last State

10 = Use Safe State

11 = Reserved

4

Format Selection

0 = Reset inputs to

zero

1 = Hold Last Value

5-7

Reserved

Reserved bits must

be zero

Entering User Parameter

Data