2–66

How Communication Takes Place and I/O Image Table Mapping

Publication 1794ĆUM057B-EN-P - November 2001

Optimal Sizes

Adapter Defaults

Module Defaults for:

Output

Default

Input

Default

Output

Default

Input

Default

Description

Catalog

Number

1794-IRT8

TC/mV/RTD Module

11

4

1

0

1794-IF4I

4 Isolated Input Module

7

8

1

0

1794-OF4I

4 Isolated Output Module

6

9

0

1

1794-IF2XOF2I

Isolated Combo Module

7

7

1

1

1794-ID2

Incremental Encoder Module

8

7

1

0

1794-IP4

Pulse Counter Module

10

3

1

0

1203ĆFM1

SCANport Module

6

5

4

3

The default values reflect the maximum number of read/write words.

You can change the I/O data size for a module by reducing the
number of words mapped into the adapter module, as shown in
optimal sizes.

Optimal sizes are the settings that provide optimal data to and from
the I/O module. You need a software configuration tool to change the
size. Make sure the FLEX I/O adapter is compatible with the
configuration tool you choose.

The optimal settings provide the fastest network time by only
mapping read and write words used by the I/O modules. If you
reduce your data sizes to only include optimal data, you can only
change your configuration data with a software tool. If you need to
change configuration information on an optimal basis, your data size
must be large enough to include the necessary words.