Mapping data into the image table – Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module User Manual User Manual
Page 24
2–4
How Communication Takes Place and I/O Image Table Mapping
Publication 1794ĆUM057B-EN-P - November 2001
Possible causes for an I/O module fault are:
•
transmission errors on the FLEX I/O backplane
•
a failed module
•
a module removed from its terminal base
•
incorrect module inserted in a slot position
•
the slot is empty
The node address changed bit is set when the node address switch
setting has been changed since power up. The new node address does
not take effect until the adapter has been powered down and then
powered back up. Until this power cycling occurs, the node address
switches will not match the actual node address.
FLEX I/O modules presently supported by the PROFIBUS adapter
are listed below. Additional modules will be added as they are
developed.
Module Description
Catalog Number
For image table
mapping, refer to:
8 Sink Input Module
1794ĆIB8
page 2-5
16 Sink Input Module
1794ĆIB16
page 2-6
8 Source Output Module
1794ĆOB8
page 2-7
16 Source Output Module
1794ĆOB16
page 2-7
16 Source Input Module
1794ĆIV16
page 2-8
16 Sink Output Module
1794ĆOV16P
page 2-9
8 Sensor Input Module
1794ĆIB8S
page 2-10
8 Electronically Fused Output Module
1794ĆOB8EP
page 2-11
10 Input/6 Output Module
1794ĆIB10XOB6
page 2-11
8 Input Module
1794ĆIA8
page 2-12
8 Output Module
1794ĆOA8
page 2-13
8 Relay Output Module
1794ĆOW8
page 2-13
8 Input Analog Module
1794ĆIE8
page 2-14
4 Output Analog Module
1794ĆOE4
page 2-17
4 in/2 out Analog Combo Module
1794ĆIE4XOE2
page 2-20
8 Input RTD Analog Module
1794ĆIR8
page 2-23
8 Input Thermocouple Module
1794ĆIT8
page 2-27
8 Input Thermocouple/RTD/mV Module
1794ĆIRT8
page 2-27
2 Input Pulse Counter Module
1794-ID2
page 2-55
4 Input Encoder Counter Module
1794-IP4
page 2-60
SCANport Module
1203ĆFM1
page 2-64
Mapping Data into
the Image Table