5–2

Troubleshooting

Publication 1794ĆUM057B-EN-P - November 2001

You can use read diagnostics to view status using the master’s
configuration software. The adapter returns identification in response
to the Read DP–Slave Diagnostic Information message.

Read DP-Slave Diagnostics Information Message

Ext_Diag_Data field (Length 9 bytes)

Octet

Description

7

Device Related diagnostic header byte (05h)

8

Revision - Minor

9

Revision - Major

10

Adapter Status

Bit 0 - Node Address Changed

Bits 1Ć7 - Reserved

11

Node Address switch setting

12

Identifier Related diagnostic header byte (44h)

13-15

Identifier diagnostic bits

1

1

One identifier bit for each logical module (adapter and each slot use

two identifier bits). The bits set indicate a module fault.

Viewing Status from the

Master's Configuration

Software