beautypg.com

Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module User Manual User Manual

Page 25

background image

2–5

How Communication Takes Place and I/O Image Table Mapping

Publication 1794ĆUM057B-EN-P - November 2001

1794ĆIB8 - 8Ćpoint Digital Input Module Image Table Mapping

Module Image

Inputs

Filter

Time

Input Size

Output Size

1 or 2 Words

0 or 1 Word

Not used

Not used

I/O Image

Read

Write

Not used

1794ĆIB8 Memory Map

Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read Words

Not used

D7

D6

D5

D4

D3

D2

D1

D0

Read

Word 1

Not used

Read

Word 2

Not used

FT 00-07

Write Word 1

Where D = Input Data (D0 corresponds to input 0, D1 corresponds to input 1, etc.

DT = Input Filter Time (DT 00-07 corresponds to inputs 0 thru 7)

1794ĆIB8 Input Filter Times

Bits

Description

Selected

02

01

00 Filter Time for Inputs 00-07

Filter Time

0

0

0

Filter Time 0 (default)

512

µ

s

0

0

1

Filter Time 1

1ms

0

1

0

Filter Time 2

2ms

0

1

1

Filter Time 3

4ms

1

0

0

Filter Time 4

8ms

1

0

1

Filter Time 5

16ms

1

1

0

Filter Time 6

32ms

1

1

1

Filter Time 7

64ms