beautypg.com

Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module User Manual User Manual

Page 44

background image

2–24

How Communication Takes Place and I/O Image Table Mapping

Publication 1794ĆUM057B-EN-P - November 2001

1794ĆIR8 Word/Bit Descriptions

Word

Dec. Bits

(Octal Bits)

Description

Read Word 1

00-15 (00-17) Reserved

Read Word 2

00-15 (00-17) Channel 0 Input data

Read Word 3

00-15 (00-17) Channel 1 Input data

Read Word 4

00-15 (00-17) Channel 2 Input data

Read Word 5

00-15 (00-17) Channel 3 Input data

Read Word 6

00-15 (00-17) Channel 4 Input data

Read Word 7

00-15 (00-17) Channel 5 Input data

Read Word 8

00-15 (00-17) Channel 6 Input data

Read Word 9

00-15 (00-17) Channel 7 Input data

Read Word 10

00-07

Underrange bits - these bits are set if the input signal is below the input channel's minimum range.

08-15 (10-17) Overrange bits - thesebits areset if 1), theinput signal is abovetheinput channel's maximum

range, or 2), an open detector is detected.

Read Word 11

00-01

Not used - set to 0

02

Reserved

03

Powerupbit - this bit is set (1) until configuration data is received by the module.

04-06

Critical Error bits - If these bits are anything other than all zeroes, return the module to the factory

for repair

07

Unused - set to 0

08 (10)

Calibration Range bit - set to 1 if a reference signal is out of range during calibration

09 (11)

Calibration Done bit - set to 1 after an initiated calibration cycle is complete.

10 (12)

Calibration Bad bit - set to 1 if the channel has not had a valid calibration.

11-15 (13-17) Unused - set to 0