1794ĆIR8 Word/Bit Descriptions
Word
Dec. Bits
(Octal Bits)
Description
Read Word 1
00-15 (00-17) Reserved
Read Word 2
00-15 (00-17) Channel 0 Input data
Read Word 3
00-15 (00-17) Channel 1 Input data
Read Word 4
00-15 (00-17) Channel 2 Input data
Read Word 5
00-15 (00-17) Channel 3 Input data
Read Word 6
00-15 (00-17) Channel 4 Input data
Read Word 7
00-15 (00-17) Channel 5 Input data
Read Word 8
00-15 (00-17) Channel 6 Input data
Read Word 9
00-15 (00-17) Channel 7 Input data
Read Word 10
00-07
Underrange bits - these bits are set if the input signal is below the input channel's minimum range.
08-15 (10-17) Overrange bits - thesebits areset if 1), theinput signal is abovetheinput channel's maximum
range, or 2), an open detector is detected.
Read Word 11
00-01
Not used - set to 0
02
Reserved
03
Powerupbit - this bit is set (1) until configuration data is received by the module.
04-06
Critical Error bits - If these bits are anything other than all zeroes, return the module to the factory
for repair
07
Unused - set to 0
08 (10)
Calibration Range bit - set to 1 if a reference signal is out of range during calibration
09 (11)
Calibration Done bit - set to 1 after an initiated calibration cycle is complete.
10 (12)
Calibration Bad bit - set to 1 if the channel has not had a valid calibration.
11-15 (13-17) Unused - set to 0