Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module User Manual User Manual

Page 46

background image

2–26

How Communication Takes Place and I/O Image Table Mapping

Publication 1794ĆUM057B-EN-P - November 2001

Description

Dec. Bits

(Octal Bits)

Word

Write Word 2

00-03

Channel 0 RTD Type

Bit

03

02

01

00

RTD Type - Range

0

0

0

0

Resistance (default)

0

0

0

1

No sensor connected - do not scan

0

0

1

0

100 ohm Pt

α

= 0.00385 Euro (-200 to +870

o

C)

0

0

1

1

100 ohm Pt

α

= 0.003916 U.S. (-200 to +630

o

C)

0

1

0

0

200 ohm Pt

α

= 0.00385 (-200 to +630

o

C)

0

1

0

1

500 ohm Pt

α

= 0.00385 (-200 to +630

o

C)

0

1

1

0

Reserved

0

1

1

1

10 ohm Copper (-200 to +260

o

C)

1

0

0

0

120 ohm Nickel (-60 to +250

o

C)

1

0

0

1

100 ohm Nickel (-60 to +250

o

C)

1

0

1

0

200 ohm Nickel (-60 to +250

o

C)

1

0

1

1

500 ohm Nickel (-60 to +250

o

C)

1

1

0

0

Module data time stamp

1101 to 1111 - Reserved

04-07

Channel 1 RTD Type (see bits 00-03)

08-11

Channel 2 RTD Type (see bits 00-03)

12-15

Channel 3 RTD Type (see bits 00-03)

Write Word 3

00-03

Channel 4 RTD Type (see write word 2, bits 00-03)

04-07

Channel 5 RTD Type (see write word 2, bits 00-03)

08-11

Channel 6 RTD Type (see write word 2, bits 00-03)

12-15

Channel 7 RTD Type (see write word 2, bits 00-03)