beautypg.com

Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module User Manual User Manual

Page 72

background image

2–52

How Communication Takes Place and I/O Image Table Mapping

Publication 1794ĆUM057B-EN-P - November 2001

Definition

Decimal Bit

(Octal Bit)

Word

Bits 00

Reserved

Bits 01

CalibrationDone bit (DN). - This bit is set to 1 after a calibration cycle is completed.

Bit 02

CalibrationBad bit (BD). - This bit is set to 1 if the channel calibrationn coefficients

cannot be saved or be read properly.

Bits 03-07

Set to 0.

Word 5

Bits 08-11

(10-12)

Reserved

Word 5

Bit 12 (14)

Set to 0

Bit 13 (15)

Configuration mode bit (CF) - This bit is set (1) when the calibration mode is

selected (bit 15, word 5 in the block transfer write set to 1).

Bit 14 (16)

Field Power Off bit (FP) - This bit is set (1) when the 24V field power fails. When

this bit is set (1), the module status indicator flashes.

Bit 15 (17)

Power Up (unconfigured state) bit (PU). - This bit is set (1) when the configuration

word is all zeroes (0) due to a reset (adapter power cycle or module insertion) or a

cleared configuration word (all 0).

Bits 00-01

Underrange bits (U). - These bits are set (1) when the input channel is below a

preset limit as defined by the configuration selected. U0 (bit 00) corresponds to input

channel 0 and U1 (bit 01) corresponds to input channel 1

Bits 02-03

WireĆOff status bits. (W). - These bits, when set (1), indicate the corresponding

current output channel is open. W0 (bit 02) corresponds to channel 0, and W1 (bit 03)

corresponds to channel 1.

Word 6

Bits 04-05

Overrange bits (V). - These bits are set (1) when the input channel is above a

preset limit as defined by the configuration selected. Bit 04 corresponds to input

channel 0 and bit 05 corresponds to input channel 1

Bits 06-09

(06-11)

Not used. Set to 0.

Bits 10-11

(12-13)

Hold output bits (P). - These bits are set (1) in response to Q0 or Q1 and a

transition of the EN bit. When P0 or P1 is set (1), they indicate that the output is

holding at the level in the readback data for the respective channel. These bits return

to 0 when the output data matches the readback output data.

Bits 12-15

(14-17)

Not used. Set to 0.

Write Word 1

Bits 00-12

(00-14)

Not used

Bit 13-14

(15-16)

Safe State Source bits (S1/S0). - When EN is 0, these bits designate the source of

the safe state data.

Bit 13 = 0, bit 14 = 1 - reset outputs to 0V/0mA

Bit 13 = 1, bit 14 = 1 - hold the output at its current level

Bit 15 (17)

Output enable bit (EN). - When set (1), the outputs are enabled. This bit must be

set in order for the real time data to appear at the outputs. If this bit is not set (0), the

outputs will be determined by S1/S0.

Word 2

Bits 00-15

(00-17)

Output Channel 0 data. Refer to Table 2.A.

Word 3

Bits 00-15

(00-17)

Output Channel 1 data. Refer to Table 2.A.