beautypg.com

Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module User Manual User Manual

Page 43

background image

2–23

How Communication Takes Place and I/O Image Table Mapping

Publication 1794ĆUM057B-EN-P - November 2001

1794ĆIR8 - RTD Input Analog Module Image Table Mapping

Module Image

I/O Image

Input Data Channel 0
Input Data Channel 1
Input Data Channel 2
Input Data Channel 3
Input Data Channel 4
Input Data Channel 5
Input Data Channel 6
Input Data Channel 7

Underrange

Calibration Mask

RTD Type

Input Size

Output Size

0 to 3 Words

1 to 11 Words

Reserved

Overrange

Calibration Status

RTD Type

Configuration

1794ĆIR8 Read

Dec. Bit 15

14

13

12

11

10

09

08

07

06

05

04

03

02

01 00

Size

Oct. Bit 17

16

15

14

13

12

11

10

07

06

05

04

03

02

01 00 Read/Write Words

Reserved

Read Word 1

Channel 0 Input Data

Read Word 2

Channel 1 Input Data

Read Word 3

Channel 2 Input Data

Read Word 4

Channel 3 Input Data

Read Word 5

Channel 4 Input Data

Read Word 6

Channel 5 Input Data

Read Word 7

Channel 6 Input Data

Read Word 8

Channel 7 Input Data

Read Word 9

Overrange Bits

Underrange Bits

Read Word 10

0

0

0

0

0

Bad

Cal

Cal

Done

Cal

Range

0

Diagnostic Status Bits

Pwr

Up

0

0

0

Read Word 11

8Ćbit Calibration Mask

Cal

Clk

Cal

Hi

Cal

Lo

Filter Cutoff

Enh

MDT

Write Word 1

RTD 3 Type

RTD 2 Type

RTD 1 Type

RTD 0 Type

Write Word 2

RTD 7 Type

RTD 6 Type

RTD 5 Type

RTD 4 Type

Write Word 3

Where:

Enh = Enhanced

MDT = Module Data Type