Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module User Manual User Manual
Page 31
2–11
How Communication Takes Place and I/O Image Table Mapping
Publication 1794ĆUM057B-EN-P - November 2001
1794ĆOB8EP - 8Ćpoint Discrete Protected Output Module Image
Table Mapping
Module Image
Outputs
Input Size
Output Size
0 or 1 Word
1 or 2 Words
I/O Image
Not used
Not used
Read
Write
Not used
Overload Fault Bits
Dec. Bits
15
14
13
12
11
10 09
08
07
06
05 04 03 02 01 00
Size
Oct. Bits
17
16
15
14
13
12 11
10
07
06
05 04 03 02 01 00 Read/Write Words
F7
F6
F5
F4
F3
F2 F1
F0
Reserved (see note)
Read 1
Not used
FR O7 O6 O5 O4 O3 O2 O1 O0 Write 1
Reserved
Write 2
Where:
F = overload fault bits - 1 = fault present; 0 = no fault
Oj = output data (O0 corresponds to output 0, O1 corresponds to output 2, etc.)
FR = fault reset bit - 1 = reset output; 0 = no change.
Note: The unused lower byte in read word 1 floats during operation. Do not use this byte for fault status.
Using the Fault Reset Button When you press the manual reset button:
1. the fault indicator for the faulted output turns off for about 1.2s (the faulted output will not attempt to turn on during this delay)
2. after the 1.2s delay, the faulted output attempts to turn on
3. if the external condition causing the fault is corrected, the output remains on, the fault indicator is off, and the status indicator is on
16Ćpoint Digital Input/Output Module Image Table Mapping -
1794ĆIB10XOB6
Module Image
Inputs
Not used
Outputs
Not used
I/O Image
Not used
Input Size
Output Size
0 or 1 Word
1 or 2 Words
Read
Write
Memory Map of 16-Point Digital Input/Output Module Image
Table – 1794-IB10XOB6
Dec. Bits 15 14 13 12 11
10 09
08
07
06
05
04
03
02
01
00
Size
Oct. Bits 17 16 15 14 13
12
11
10
07
06
05
04
03
02
01
00 Read/Write Words
Not used
I9
I8
I7
I6
I5
I4
I3
I2
I1
I0
Read word 1
Not used
Read word 2
Not used
O5 O4 O3 O2 O1
O0
Write word 1
Where
I = Input Channel
O = Output Channel