How Communication Takes Place and I/O Image Table Mapping

Publication 1794ĆUM057B-EN-P - November 2001

Adapter Input Status Word

The input status word consists of:

I/O module fault bits – 1 status bit for each slot

node address changed – 1 bit

15

Bit:

0

1

2

3

4

5

6

7

Reserved

I/O Module Fault Bits

Node Address Changed Bit

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Slot 6

Slot 7

Slot 8

8

14 13 12 11 10 19

The adapter input status word bit descriptions are shown in the
following table.

Bit Description

Bit

Explanation

8

This bit is set (1) when an error is detected

in slot position 1.

9

This bit is set (1) when an error is detected

in slot position 2.

10

This bit is set (1) when an error is detected

in slot position 3.

I/O Module Fault

11

This bit is set (1) when an error is detected

in slot position 4.

I/O Module Fault

12

This bit is set (1) when an error is detected

in slot position 5.

13

This bit is set (1) when an error is detected

in slot position 6.

14

This bit is set (1) when an error is detected

in slot position 7.

15

This bit is set (1) when an error is detected

in slot position 8.

Reserved

1-7

Reserved

Node Address

Changed

0

This bit is set (1) when the node address

switch setting has been changed since

power up.