Rockwell Automation 1794-APB/B FLEX I/O PROFIBUS Adapter Module User Manual User Manual
Page 47
2–27
How Communication Takes Place and I/O Image Table Mapping
Publication 1794ĆUM057B-EN-P - November 2001
1794ĆIT8 - Thermocouple Input Module Image Table Mapping
Module Image
I/O Image
Input Data Channel 0
Input Data Channel 1
Input Data Channel 2
Input Data Channel 3
Input Data Channel 4
Input Data Channel 5
Input Data Channel 6
Input Data Channel 7
Underrange
Calibration Mask
Thermocouple Type
Input Size
Output Size
0 to 3 Words
1 to 11 Words
Reserved
Overrange
Calibration Status
Thermocouple Type
Configuration
1794ĆIT8 Read and Write Words
Dec. Bit 15
14
13
12
11
10
09
08
07
06 05 04
03
02
01
00
Size
Octal Bit 17
16
15
14
13
12
11
10
07
06 05 04
03
02
01
00
Read/Write Words
Reserved
Read Word 1
Channel 0 Input Data
Read Word 2
Channel 1 Input Data
Read Word 3
Channel 2 Input Data
Read Word 4
Channel 3 Input Data
Read Word 5
Channel 4 Input Data
Read Word 6
Channel 5 Input Data
Read Word 7
Channel 6 Input Data
Read Word 8
Channel 7 Input Data
Read Word 9
Overrange Bits
Underrange Bits
Read Word 10
0
0
0
0
0
Bad
Cal
Cal
Done
Cal
Range
0
Diagnostics
Pwr
Up
Bad
Structure
CJC
over
CJC
Under
Read Word 11
8ĆBit Calibration Mask
Cal
Clk
Cal
hi
Cal
lo
Filter Cutoff
FDF
Data Type
Write Word 1
Thermocouple 3 Type
Thermocouple 2 Type
Thermocouple 1
Type
Thermocouple 0 Type
Write Word 2
Thermocouple 7 Type
Thermocouple 6 Type
Thermocouple 5
Type
Thermocouple 4 Type
Write Word 3
Where:
FDF = fixed digital filter bit