Using I/O Configuration Software

E–2

Publication 1771Ć6.5.99 - December 1995

Channel Setup Screen

1771–CFM Series A Channel Setup Rack–Group–Module: 0–0–0

channel 0 channel 1 channel 2 channel 3

current values:

channel mode high–res freq (not used) totalizer noreset totzr

frequency 43.0 15,487 258

total counts ––– 3,881,128 1,111,111

acceleration 0 359 0

–––––––––––––––––––– channel 0 channel 1 channel 2 channel 3

new channel mode high–res freq (not used) totalizer noreset totzr

minimum sample time 10 ms 1000 ms 0 = 100 ms

for frequency

acceleration 2,000 5,000 disabled

alarm value

accel sample time 100 rolling avg –––

(freq intervals)

highest allowed 60,000 0 0

frequency

Press F9(Toggle) to change channel mode.

Rem RUN mod 1 of 1 Addr#42:CFM4B

Change I/O Output Monitor BT Data Default Toggle Accept

Mode Ovrview Setup Tables Config

F1 F2 F4 F5 F6 F8 F9 F10

Cursor to

BT instruction

I/O Module

System Overview

F3

F2

Edit

Channel Setup

or

a

b

Output Setup

or Monitor

or BT Data

c

F2

F10

Edit

I/O Edit

or

Choose one:

Use PageUp or PageDown to move

through the channel setup screens.

Ladder Editor

Main Menu

Shows current values for each channel

(these values reflect the data received

the last time a BTR was completed).
The PLC processor must be in Run

mode if you want to receive current data

from the CFM module.

Shows current programming

for each channel and lets you

change the channel programming.
Fields inapplicable in the

programmed channel mode are

shown as dashes

and cannot be edited.

Press

(F3)

Ć

Channel Setup

to configure individual channels or

(F10)

-

Accept

to accept

your edits. We suggest that you complete your edits on all screens before accepting the edits.

–––––––––––––––––––– channel 0 channel 1 channel 2 channel 3

scalers for total ––– 1/2 1/1

(multiply/divide)

rollover value ––– 0 5,000,000

tied to outputs 0,2,3 1 none

reset total ––– disabled –––

reset overflow ––– disabled disabled

start prover ––– enabled enabled

prover type, uni ––– bi uni

or bidirectional

Enter rollover value (0 to 9,999,999).

>

Rem RUN mod 1 of 1 Addr#42:CFM4B

Change I/O Output Monitor BT Data Default Accept

Mode Ovrview Setup Tables Config

F1 F2 F4 F5 F6 F8 F10

–––––––––––––––––––– channel 0 channel 1 channel 2 channel 3

lowest measurable 1 Hz ––– –––

frequency

end sample on time only ––– –––

counts to end ––– ––– –––

sampling

frequency resolution 0.1 Hz ––– –––

frequency scalers 1/1 1/1 1/60

(multiply/divide)

Press F9(Toggle) to change bandwidth limit.

Rem RUN mod 1 of 1 Addr#42:CFM4B

Change I/O Output Monitor BT Data Default Toggle Accept

Mode Ovrview Setup Tables Config

F1 F2 F4 F5 F6 F8 F9 F10